Gas Burners

Heat release max. 350 kW

  • Guaranteed electromagnetic compatibility
  • No high-voltage cable required on site
  • Protection ratings of IP 54 (standard) or IP 65 (special version)
  • Rugged, low-maintenance design
  • Service friendly design: All electrical components are easy to replace
  • Nine burner sizes ranging from 15 kW to 4.5 MW (50,000 BTU/hr to 15,000,000 BTU/hr)
  • Built-in flame rod, ideally located
  • EC-approved ionisaton flame monitors and burner controls
  • Fuel types include natural gas, conditioned coke oven gas, propane/butane or process gas, according to customer preference and analysis
  • 1-stage, 2-stage or modulated operation
  • Wide turn down ratio
  • Custom outer tube lengths available in 10-mm increments

Applications

  •     Steel industry
  •     Light metal industry
  •     Brick and ceramic industries
  •     Process applications (chemical, refinery)

Approvals

(*) Certifications of the integrated ionisation flame monitor

(*) Certification of the integrated burner control

 

Certifications of the integrated ionisation flame monitors (*):

(*) Option: Main flame monitor may be provided by client

Certifications of the integrated ionisation flame monitor (*):

(*) Main flame monitor may be provided by client

Technical Data

200 kW350 kW800 kW
Data
Outer tube diameter90 mm135 mm160 mm
Turn down ratio 10 : 110 : 110 : 1
Outer tube length 200 – 2000 mm360 – 4000 mm360 – 4000 mm
Gas port Rp 3/4, rotatable 4 x 90°Rp 1, rotatable 4 x 90°Rp 2, top or bottom
Air portRp 2, rotatable 4 x 90°DN 80 / PN 6, rotatable 4 x 90°DN 100 / PN 6, rotatable 4 x 90°
Power head
Ignition 5 kV against ground5 kV against ground2 x 5 kV against ground
Ambient temperature- 30 °C to + 60 °C
(BA2/BDA2)
- 30 °C to - 85 °C (BR2/BD2)
- 30 °C to + 60 °C
(BA3/BDA3)
- 30 °C to - 85 °C (BR3/BD3)
- 30 °C to + 60 °C
(BA4/BDA4)
- 30 °C to - 85 °C (BR4/BD4)
Protection ratingIP54/IP65IP54/IP65IP54/IP65
Models
with integrated spark transfomer and ionisation flame monitor for intermittent operationBA2...BA3...BA4...
with integrated spark transfomer and ionisation flame monitor for continuous operationBDA2...BDA3...BDA4...
with integrated spark transfomer and burner control for intermittent operation BR2...BR3...BR4...
with integrated spark transfomer and burner control for continuous operationBD2...BD3...BD4...

Certificates

The certificates are available for logged-in partners only.

Your contact options

Email

Contact

Sales

Sales

Service

Service