Gas Fired Igniters

Heat release max. 2 kW

  • Compact design with integrated spark transformer and ionisation flame monitor/burner control
  • Built-in flame rod, ideally located
  • No high-voltage cable required on site
  • Guaranteed electromagnetic compatibility
  • Rugged, low-maintenance design
  • Sizes ranging from 2 kW to 10 MW (7,000 BTU/hr to 35,000,000 BTU/hr)
  • Custom outer tube lengths available in 10-mm increments
  • Fuel types include natural gas, conditioned coke oven gas, propane/butane or process gas, according to customer preference and analysis
  • Extremely tight and long pilot flame - no automatic retraction system typically required
  • Class 1, 2 or 3 gas fired igniters according to NFPA also available
  • Also available with flexible outer tube for tilting burners

Applications

  • Ignition of gas burners up to 500 kW
  • Application in heat treatment plants and where space is limited

Approvals

(*) Certifications of the integrated ionisation flame monitor

(*) Certifications of the integrated ionisation flame monitor

(*) Certifications of the integrated ionisation flame monitor

Technical Data

2 kW4 kW45 kW
Common data
Outer tube diameter15 mm25 mm35 mm
Flame length (depending on the gas)max. 80 mmmax. 100 mmmax. 500 mm
Outer tube length L120 – 2400 mm120 – 4000 mm240 - 15000 mm
Gas portRp 1/4Rp 1/4Rp 1/2, left or right
Gas pressure inlet20 mbarg (up to 2 m)20 mbarg, depending on the outer tube length50 - 150 mbarg
Air portRp 1/4Rp 3/8, rotatable 4 x 90°Rp 1, rotatable 4 x 90°
Air pressure operating 20 mbarg (up to 2 m)20 mbarg (up to 2 m)≥15 mbarg, depending on the outer tube length
Power head (not ZGF/ZGU/ZGP)
Ignition5 kV against ground5 kV against ground5 kV against ground
Ambient temperature- 30 °C to + 60 °C- 30 °C to + 60 °C- 30 °C to + 60 °C
Protection ratingIP 54 or IP 65IP 54 or IP 65IP 54 or IP 65
Models
without electrical componentsZGF...ZGU...ZGP...
with integrated spark transformerZTF...ZTU...ZTP...
with integrated spark transformer and ionisation flame monitor for intermittent operationZAF...ZAU...ZAP...
with integrated spark transformer and ionisation flame monitor for continuous operationZDAF...ZDAU...ZDAP...