Tube Ø38 mm explosionproof

Gas Fired Igniters

Ignition of main burners in furnaces, boilers, power plants and incinerators.

Overview

  • High energy ignition, Insensitive to moisture
  • Material burner tube stainless steel 310/321
  • Material connection enclosure stainless steel 316
  • Self-aspirating, forced air supply or combination
  • For self-aspirating version no air supply line required
  • Insensitive to pressure fluctuations (draft and windbox)
  • Integrated spark plug and ionisation electrode
  • Explosion proof ATEX II 2G Ex e IIC T6/T5 Gb/-, DEK 11 ATEX 0032; IECEX DEK11.0010
  • Option for ATEX II 2G Eex d IIC T6 PTB 03 ATEX 1190, GOST R execution
  • Min. and max. temperature for connection enclosure: -40 to 80 °C, IP66
  • Electrical connection, 2 x M20x1,5 mm cable gland
  • Connection to main burner: 1½" Ansi 150 LBS RF - Gas connection: ½" NPTF

 

 

Applications

  • Main burners of furnaces, boilers, incinerators and power plants

Technical Data

Tube Ø38 mmTube Ø38 mm explosionproof
Self-aspirating ignition burner
type38AVS-L-A-VE38AVEXE-L-A-VE
heat release with natural gas17–29 kW17–29 kW
heat release with propane24–39 kW24-39 kW
min. max pressure0.5–1.5 Barg0,5 - 1,5 Barg
length L400, 500 600: multiple of 100 mm from 1000 to 2000: 200 mm intervals 2000, 2500, 3000 mmFrom 400 to 3000 mm
air inlet A≥300 mm in steps of 10 mm> 300 mm
connection to main burnerflange 1½" ANSI 150 LBS RFFlange 1 1/2" ANSI 150 Lbs RF
gas connection1/2" NPTF1/2" NPTF
air connection, for forced draftoption1/2" NPTF
ignitionby 1 integrated spark plugHigh energy, one sparkplug
flame detectionionisationIonisation
tube material310 and 321 SST310 and 321 SST
connection material316 SST316 SST
electrical connectionM25 connector for ignition, M25 connector for ionisationExplosion proof connection housing
protectionIP65IP66

Your contact options

Email

Contact

Sales

Sales

Service

Service