BWO

High energy ignition device

The BWO ignition device is suitable for the reliable ignition of gases in ignition burners and pilot burners used in furnaces, boilers and incinerators in various industries.

The electronic unit is equipped with a fail-safe ionisation flame relay which allows to connect easily to the ionisation rod of the designated ignition burner and realize the flame detection of the burner hassle-free. In addition the contact for remote start can be used for convenient operation out of the control room.

The main electronic is installed in an explosion proof housing of type Ex d while simple wiring is possible due to the terminals located in an Ex e housing. Both are industrial made and robust for long-lasting installations.

Overview

  • Ignition of gaseous or light liquid fuels
  • Suitable for ignition or pilot burners
  • Integrated flame relay for ionisation flame monitoring
  • Ready-to use contact for remote start
  • Thyristor controlled and therefore non-wearing electronic

Applications

  • Chemical industry
  • Refineries

Technical data

Electrical connection24 / 115 / 230 VAC, 50-60 Hz
Power consumption37 VA
Ignition voltage2000 V
Ignition energy / spark8 J
Ignition energy / second16 J
Ignition frequency2 sparks / second
Power on time (max)540 sec (ED 33%*)
Flame detectionIonisation flame monitoring
Contacts / Output signalsFlame ON / OFF
Remote ignition control
Max distance to ignition position30 m
(*ED = duration of sparking)
Version for use in Hazardous areasHazardous areas
Enclosure materialStainless steel/aluminum,
painted
Steel,
painted
Perm. ambient temperature-20... +55°C-20... +40°C
ProtectionIP66IP65
Explosion protectionII 2G Ex de IIC T6II 2G EEx de IIC T6
One ignition burnerEnclosure
stainless steel/aluminum
painted, heated
Enclosure
steel, painted
Product codeBWO(BG)2/2-SV98H-CR-PHBWO(EE)2/2-SV98H-CR
Number of ignition units11
Max power consumption137 VA
(incl. panel heater (PH))
37 VA
Ignition energy / spark8 J8 J
Ignition frequency2 sparks / second2 sparks / second
Number of contacts1x Flame ON / OFF
1x Ignition control
1x Flame ON / OFF
1x Ignition control
Number of enclosures11
Perm. ambient temperature-40... +55°C-20... +40°C
ProtectionIP66
II 2G Ex de IIC T6
IP65
II 2G EEx de IIC T6
Dimensions (appr.)276 x 576 x 217 mm235 x 605 x 268 mm
Weight (appr.)21 kg42 kg