Gas Fired Igniters
Heat release max. 45 kW
- Compact design with integrated spark transformer and ionisation flame monitor/burner control
- Built-in flame rod, ideally located
- No high-voltage cable required on site
- Guaranteed electromagnetic compatibility
- Rugged, low-maintenance design
- Sizes ranging from 2 kW to 10 MW (7,000 BTU/hr to 35,000,000 BTU/hr)
- Custom outer tube lengths available in 10-mm increments
- Fuel types include natural gas, conditioned coke oven gas, propane/butane or process gas, according to customer preference and analysis
- Extremely tight and long pilot flame - no automatic retraction system typically required
- Class 1, 2 or 3 gas fired igniters according to NFPA also available
- Also available with flexible outer tube for tilting burners
Applications
- Ignition of medium-sized gas and oil burners in industrial furnaces and boilers
Approvals
(*) Certifications of the integrated ionisation flame monitor
(*) Certifications of the integrated ionisation flame monitor
(*) Certifications of the integrated ionisation flame monitor
Technical Data
45 kW | |
Common data | |
Outer tube diameter | 35 mm |
Flame length (depending on the gas) | max. 500 mm |
Outer tube length L | 240 - 15000 mm |
Gas port | Rp 1/2, left or right |
Gas pressure inlet | 50 - 150 mbarg |
Air port | Rp 1, rotatable 4 x 90° |
Air pressure operating | ≥15 mbarg depending on the outer tube length |
Power head (not ZGP) | |
Ignition | 5 kV against ground |
Ambient temperature | -30 °C to +60 °C |
Protection rating | IP 54 or IP 65 |
Models | |
without electrical components | ZGP... |
with integrated spark transformer | ZTP... |
with integrated spark transformer and ionisation flame monitor for intermittent operation | ZAP... |
with integrated spark transformer and ionisation flame monitor for continuous operation | ZDAP... |
45 kW Ex-zone 1 / 21 | |
Common data | |
Outer tube length L | 240 - 10000 mm |
Gas port | Rp 3/4, top or bottom |
Gas pressure inlet | 50 - 150 mbarg |
Air port | Rp 1½, rotatable 4 x 90° |
Air pressure operating | min. 10 mbarg, depending on the outer tube length |
Power head | |
Ignition | 5 kV against ground, |
Ambient temperature | -20 °C to +60 °C (standard), -30 °C to +75 °C special version) |
Protection rating | IP 66 |
Models | |
Heat release 45 kW | ZAVEX/P... |
45 kW Ex-zone 2 / 22 | |
Common data | |
Outer tube length L | 240 - 15000 mm |
Gas port | Rp 1/2, left or right |
Gas pressure inlet | 50 - 150 mbarg |
Air port | Rp 1, rotatable 4 x 90° |
Air pressure operating | min. 10 mbarg, depending on the outer tube length |
Power head | |
Ignition | 5 kV against ground |
Ambient temperature | -20 °C to +60 °C |
Protection rating | IP 65 |
Models | |
Heat release | 45 kW |
with integrated spark transformer and ionisation flame monitor for intermittent operation | ZXAP... |
with integrated spark transformer and ionisation flame monitor for continuous operation | ZXDAP... |
45 kW | |
Common data |
|
Outer tube diameter (stainless steel tube) | 48 mm, max. 52 mm |
Flame length | depending on igniter size |
Outer tube length L | 800 - 0000 mm |
Gas pressure inlet | 50 - 150 mbarg |
Power head (not ZG...) | |
Ignition | 5 kV against ground |
Ambient temperature | -30 °C to +60 °C |
Protection rating | IP 54 or IP 65 |
Models | |
without electrical components | ZGPF... |
with integrated spark transformer | ZTPF... |
with integrated spark transformer and ionisation flame monitor for intermittent operation | ZAPF... |
with integrated spark transformer and ionisation flame monitor for continuous operation | ZDAPF... |