Self-aspirating gas fired igniters
Tube Ø48.3 mm
Self-aspirating gas fired igniters guarantee the reliable and safe ignition of main burners in furnaces and boilers if no air supply lines are available. SMITSVONK gas igniters of size Ø48.3 mm can be equipped with up to four additional gas tubes for increased heat release.
The design is insensitive to moisture as the initial ignition is based on the proven high energy ignition technology of SMITSVONK. Integrated long-lasting spark plugs and ionisation electrodes assure a long service life with a minimum of downtime for maintenance.
The intake of combustion air is easily adjusted at all models. If needed the conversion to a forced-air gas fired igniter is possible with little effort.
Overview
- Insensitive to pressure fluctuations
- For all kind of gases and pressures
- Durable stainless steel construction
- ATEX and IECEx approved versions for hazardous area use
- Rugged design for harsh environmental conditions
Applications
Ignition of main burners in furnaces, boilers, incinerators in
- Petrochemical industry
- Refineries
- Power plants
Technical data
Tube diameter | 48,3 mm |
Tube length (L) | 400 - 3000 mm, in steps of 100, 200 and 500 mm |
Air inlet position (A) | 175 mm, ≥300 mm, in steps of 10 mm |
Additional gas tubes | 1, 2, 4 |
Connection to main burner | Mounting flange, 2" ANSI 150 lbs RF |
Gas connection | 1/2" NPTF (flange optional) |
Air connection | Optional (1/2" BSPF provided) |
Electrical connection | 2x M20, for ignition and flame detection |
Ignition | High energy ignition, 1 spark plug, integrated |
Flame detection | Ionisation electrode, integrated Thermocouple (optional) |
Material enclosure / tube | Stainless steel: 310, 316 |
Material connection | Stainless steel: 316 |
Perm. temperature range | -40...+80°C |
Version for use with | Natural gas | Propane |
---|---|---|
Type designation | L48AV...-V_E-... | L48PV...-V_E-... |
Heat release (min - max) | 17 - 250 kW | 22 - 370 kW |
Minimum pressure | 0.2 barg | 0.2 barg |
Maximum pressure | 0.8 barg | 0.8 barg |
Version for use in | Safe areas | Hazardous areas |
---|---|---|
Product code | L48AV13JB-1000-300-V | L48PV13EXE-1200-450-VHT-2E-FA... |
Gas type | Natural gas | Propane |
Heat release | 46 - 75 kW | 120 - 195 kW |
Tube diameter | 48.3 mm | 48.3 mm |
Tube length (L) | 1000 mm | 1200 mm |
Air inlet position (A) | 300 mm | 450 mm |
Flame detection | Ionisation rod, max 280°C | Ionisation rod, high temperature, >280°C |
Extra gas tubes | 0 | 2 |
Gas connection | Screwed, 1/2" NTPF, standard | Flanged, 1/2" ANSI 150 lbs RF |
Protection | IP66 | IP66 II 2G Ex e IIC T5 II 2G Ex e IIC T6 |