Z 726 K
Burner control
Self-monitoring and fail-safe burner controls for the integration into the Hegwein burners and igniters.
Overview
- Controlling and monitoring of gas and oil burners/gas and oil fired igniters of any capacity
- Suitable for intermittent operation (Z 726 K2...) and continuous operation (Z 726 K3..., Z 726 KH..., Z 726 KE...)
- Optional pre-purge of the combustion chamber with changeable pre-purge time and air pressure check
- Optional changeable safety times
- Optional input for external flame monitor
- Optional re-cycling after flame loss in operating position
- For Z 726 KH... und Z 726 KE...: Bargraph display and config-switch
- For Z 726 KE...: Complete function range with 16-pin plug connector for not safety-related 4 - 20 mA output signal
Applications
- Chemical industry
- Refineries
- Cement plants
- Waste incinerators
- Steam generators
- Heating plants
- Industrial furnaces
Technical Data
Z 726 K | |
Operational mode | Intermittent Operation (Z 726 K2...) and Continuous Operation (Z 726 K3..., Z 726 KH..., Z 726 KE...) |
Safety | Self-monitoring and fail-safe |
Mains voltage | 230 VAC +10%/-15% (standard Z 726 K.../000) |
Mains voltage | 115 VAC +10%/-15% (special version Z 726 K.../00M) |
Mains frequency | 50/60 Hz +/-5% |
Power consumption | 20 VA |
Pre-purge time | 0 s (optional 30/60/120 s) |
First safety time | 3 s (optional 5/10/15 s) |
Flame failure response time | 1 s (optional 2/3/5 s) |
Flame intensity | 0 - 50 µA |
Output signal (optional) | 4 - 20 mA (not safety-related) |
Admissible ambient temperature | - 30 °C to + 85 °C |
Installation | Integration into burner/igniter enclosure |
Protection rating | IP 54 (front) When in a mounted condition, protection rating IP 54 must be ensured as a minimum requirement. |
Display | LEDs |
Weight | approx. 0,9 kg |
Dimensions | 122 x 124 x 140 mm (WxHxD) |