D-VTA 200

For fossil fuel power plants

The D-VTA 200 Thermography Analysis System is developed, to work with all DURAG D-FS Furnace Sensors. Up to 8 Furnace Sensors can be connected to one D-VTA 200 System.

Together with the Furnace Sensor, the software delivers online temperature distributions directly from the combustion chamber.

The temperature range and the resolution are depending on the Furnace Sensor.

Depending on the application different analysing software modules are available.

Basic System

Hardware:

  • 19" industrial PC incl. 24" LED monitor
  • Industrial Mainboard long-term available
  • Power supply 110/230VAC, 50-60Hz, 400W

Software:

  • Live and Thermography Image
  • Free defineable ROIs (Region Of Interest) for measuring the temperature
  • Video recording to HDD
  • Remote control of Furnace Sensor and the Retraction Unit
  • Historical Alarm Display
  • SQL database with historical storage for one year
  • SQL to ASCII export, for importing into Excel
  • User defineable historical Trend Display
  • Limo (Line Of Interest) function and history
  • Operating System: Linux

Your Benefit

  • Enhance combustion Efficiency
    Depending on the boiler type and used fuels it's possible to optimise the temperture distribution. In some installtions it's possible to see the soot on the walls.
      
  • Less tube ruptures, reduce down time
    The detection and optimisation of the fireball will help to have less tube ruptures, because the the flames will not heat the tubes partly to much.
  • Optimisation aid in case of chaning load or fuels
    Many fossil fuel boiler has to change there loads many times a week and has to go down below 25% of load. In this low conditions the Furnace Sensor can be used to monitor the lower elevatons and see if the flames are getting unstable. Also the System can be used to change faster from oil to coal.

Fireball

Image Fireball

The D-VTA 200 Fireball software is designed for the use in tangential fired boiler.

The software calculates the position of the fireball and draws the position in the thermo image. The actual position can be compared with a defineable optimal position.

The values can be sent over a process connecton to the DCS and can be used to optimise the combustion.

Additional Software

D-VTA 200 WEB

  • WebServer for remote view over LAN/Internet with a web-browser
  • Live and Thermography Images
  • System status
  • Data Export to local ASCII-files

D-VTA 200 AutoVideo

  • Separate HDD for automatic video records of the last 10 days

Process Connections

  • D-VTA 200 MODBUS RTU
  • D-VTA 200 MODBUS TCP/IP
  • D-VTA 200 PROFIBUS

Downloads

Declarations of conformity

Your contact options

Email

Contact

Sales

Sales

Service

Service