- Compact design with integrated spark transformer and ionisation flame monitor/burner control
- Built-in flame rod, ideally located
- No high-voltage cable required on site
- Guaranteed electromagnetic compatibility
- Rugged, low-maintenance design
- Custom outer tube lengths available in 10-mm increments
- Fuel types include natural gas, conditioned coke oven gas, propane/butane or process gas, according to customer preference and analysis
- Extremely tight and long pilot flame - no automatic retraction system typically required
- Class 1, 2 or 3 gas fired igniters according to NFPA also available
- Also available with flexible outer tube for tilting burners
Applications
- 6000 kW Gas Fired Igniters Class 1, 2 or 3
- Ignition and warm-up of boilers according to American standard
Approvals
(*) Certifications of the integrated ionisation flame monitor
(*) Certifications of the integrated ionisation flame monitor
(*) Certifications of the integrated ionisation flame monitor
Technical Data
6000 kW NFPA | |
General data | |
Outer tube diameter | 90 mm |
Flame length | max. 4000 mm |
Outer tube length L | 240 - 10000 mm |
Gas port | Rp 2, bottom |
Main gas port | |
Gas pressure inlet | 1 barg |
Air port | Rp 2, rotatable 4 x 90° |
Air pressure operating | ≥ 10 mbarg |
Power head | |
Ignition | 2 x 5 kV, ignition electrode against ignition electrode |
Ambient temperature | -30 °C to +60 °C |
Protection rating | IP 54 or IP 65 |
Model | |
with integrated spark transformer and ionisation flame monitor for intermittent operation | PA2... |
with integrated spark transformer and ionisation flame monitor for continuous operation | PDA2... |