D-FW 240 EX

Filter Monitor

Filter monitor to detect the efficiency and function of filters and filtration systems. Dust Monitor for qualitative measurement of dust concentration in the dry process or flue gas.

Overview

  • In situ measurement, continuous measurement
  • Ex proof design
  • Qualitative dust measurements for monitoring the functions of filters
  • One-sided mounting on the channel
  • No moving parts, even within the duct
  • Easy installation, adjustment and maintenance without a PC

Your benefit

  • Compact and cost effective solution
    Small housing and low system cost
  • Rugged design for harsh environmental conditions
    Suitable for a wide range of application due to heavy duty metal housing designed for EX environments
  • Space-saving and easy installation
    One-sided Installation without alignment and the simple measuring principle with analog output allows easy installation and setup
  • Low operation costs
    No purge air required
  • Suitable for harsh flue gas pressure conditions
    The filter monitor is suitable for flue gas pressure up to 500 hPa

Applications

  • Power Plants
  • Bag filter houses of any kind
  • Dust in the manufacturing industry

The measuring principle does not allow installation directly behind electrostatic filters.

Technical Data

Measured componentdust load
Flue gasair, flue gas, process gas
Flue gas dust concentration1 ... 25 to 20 ... 400 mg/m3
Flue gas flow velocity> 7 m/s
Stack/ duct inner diameter> 0.15 m
Flue gas temperature-20 ... +200 °C
Inner stack/duct pressure
(relative to ambient pressure)
-500 ... +500 hPa
Flue gas humidity20 ... 80% rel. humidity
Ambient temperature-20 ... +50 °C
Measuring principleMeasuring the transfer of electrical charge from dust particles to an electrode in flowing sample gas
Type, mounting location4 (7) wire transmitter, in situ, mounted at stack, probe is in contact with sample gas
System ComponentsD-FW 240Ex M M Measuring device
D-FW 231 P probe
Measuring ranges0 ... 100% Tribo-value, 6 per micro DIP switch selectable ranges
Output range0 ... 100% Tribo value
Process connectionG1" female thread, tube ID >= 36mm, L max. 100 (300*) mm
Analog output1 x 4 ... 20 mA, 500 Ohm
Digital input2 x Transistor-Input for zero check, integration
Power supply24 V DC +- 10%; 0.1 A
IP protection class (IEC 60529),
Explosion protection
IP65
EX II 2G EEx d ib IIC T6 Gb
EX II 2G/D EEx d ib IIC T6 td A21 ibD 21 IP65 T 105°C
PTB 04 ATEX 1037
Dimensions (hxwxd)180 x 80 x 270 mm (without D-FW 231 P Probe)
Weight1.9 kg
MaterialHousing: Al Alloy, painted RAL 5017
Probe connector: 1.4571
Isolator: PTFE (standard), ceramic (option)
DimensionsLength: 80, 250, 400, 700, 1000 mm
Material1.4571
Remarks
  • The suitability of D-FW 240Ex for the listed ranges depends upon the kind of dust and its size distribution.
  • The measuring effect is dependant upon the flow speed. 
  • Subject to technical modifications!